PRODUCTS
|
Engine
speed
rev/min |
Type
of Operation |
Typical
Generator Output (net) |
Engine Power Gross |
| kWe |
kVA |
kW |
bhp |
| 1500 |
Prime
Power
Standby (maximum) |
50.8
55.8 |
63.5
69.8 |
56.4
62.0 |
75.6
83.1 |
| 1800 |
Prime
Power
Standby (maximum) |
57.2
63.0 |
71.6
78.8 |
63.6
70.0 |
85.3
93.9 |
|
|
| Typical Fuel Consumption |
| rev/min |
1500
rpm |
1800 rpm |
| |
litre/hr |
UK
gall/hr |
litre/hr |
UK
gall/hr |
| At 110% of power rating |
15.8 |
3.48 |
18.0 |
3.96 |
| At 100% of power rating |
14.8 |
3.26 |
16.9 |
3.72 |
| At 75% of power rating |
10.2 |
2.24 |
13.2 |
2.90 |
| At 50% of power rating |
5.5 |
1.21 |
9.0 |
1.98 |
|
|
| Note: All engine rating data based on operation under BS5514:1996, ISO 3046/1:1995 and DIN 6271 conditions. |
| Test
Conditions |
Air temperature 25°C (80.6°F), barometric pressure
100 kPa (29.5 in Hg), relative humidity 30%, maximum exhaust back
pressure 6 kPa, maximum inlet restriction 3 kPa.
For operation outside of these conditions please consult your Perkins
or Sabre Engines contact.
Performance tolerance quoted by Perkins is ±5%.
Electrical ratings assume a power factor of 0.8 and a generator efficiency
of 90%. |
|
|
|
| Rating
Definitions |
Prime power: Power available at variable load in lieu of main power network. An overload of 10% is permitted for one hour in every twelve hours of operation.
Standby (maximum): Power available at variable load in the event of a main power network failure. No overload is permitted. |
|
|
|
|