PRODUCTS
|
Engine
speed
rev/min |
Type
of Operation |
Typical
Generator Output (net) |
Engine Power Gross |
| kWe |
kVA |
kW |
bhp |
| 1500 |
Prime
Power
Standby (maximum) |
67.5
74.3 |
84.4
92.8 |
75.0
82.5 |
100.6
110.6 |
| 1800 |
Prime
Power
Standby (maximum) |
74.4
81.9 |
93.0
102.4 |
82.7
91.0 |
110.9
122.0 |
|
|
| Typical Fuel Consumption |
| rev/min |
1500
rpm |
1800 rpm |
| |
litre/hr |
UK
gall/hr |
litre/hr |
UK
gall/hr |
| At 110% of power rating |
20.4 |
4.49 |
24.1 |
5.30 |
| At 100% of power rating |
19.0 |
4.18 |
22.0 |
4.84 |
| At 75% of power rating |
14.3 |
3.15 |
16.6 |
3.65 |
| At 50% of power rating |
9.5 |
2.09 |
11.8 |
2.60 |
|
|
| Note: All engine rating data based on operation under BS5514:1996, ISO 3046/1:1995 and DIN 6271 conditions. |
| Test
Conditions |
Air temperature 25°C (80.6°F), barometric pressure
100 kPa (29.5 in Hg), relative humidity 30%, maximum exhaust back
pressure 6 kPa, maximum inlet restriction 3 kPa.
For operation outside of these conditions please consult your Perkins
or Sabre Engines contact.
Performance tolerance quoted by Perkins is ±5%.
Electrical ratings assume a power factor of 0.8 and a generator efficiency
of 90%. |
|
|
|
| Rating
Definitions |
Prime power: Power available at variable load in lieu of main power network. An overload of 10% is permitted for one hour in every twelve hours of operation.
Standby (maximum): Power available at variable load in the event of a main power network failure. No overload is permitted. |
|
|
|
|