EngineSales@Perkins-Sabre.com     PartSales@Perkins-Sabre.com
 


PRODUCTS

Performance - 422GM
Description Specifications Performance Equipment Installation Drawings
 
Engine speed
rev/min
Type of Operation Typical Generator Output (net) Engine Power Gross
kVA kWe kW bhp
1500 Prime Power
Standby (Maximum)
20.7
22.8
16.6
18.2
18.4
20.24
24.7
27.1
1800 Prime Power
Standby (Maximum)
24.8
27.2
19.8
21.8
22.0
24.2
29.5
32.5
 
Typical Fuel Consumption
Engine speed 1500 rev/min 1800 rev/min
g/kWh l/hr g/kWh l/hr
At Standby Rating 254 6.2 252 7.3
At Prime Power 243 5.4 245 6.4
At 75% Prime Power 243 4.0 247 4.8
At 50% Prime Power 265 2.9 269 3.5
 
Note: The above ratings represent the engine performance capabilities to conditions specified in ISO 8528/1, ISO 3046/1:1986, BS5514/1

Derating may be required for conditions outside these; consult your Perkins Sabre contact

Generator powers are typical and are based on typical alternator efficiencies of 90% and a power factor (cos.0) of 0.8

Fuel specification: BS 2869: Part 2 1998 Class A2 or ASTM D975 D2

Lubricating oil: To API CH4/ACEA E5
 
Rating Definitions
Prime power: Power available at variable load in lieu of main power network. Overload of 10% is permitted for one hour in every 12 hours of operation

Standby (maximum): Power available at variable load in the event of a main power network failure. No overload is permitted