Engine speed
rev/min
Type of Operation Typical Generator Output Nett Engine Power
kVA kWe kWm bhp
1500 Prime Power
Standby Power
145.9
160.4
116.7
128.3
125.5
138.0
168.2
184.9
1800 Prime Power
Standby Power
169.8
187.1
135.8
149.7
146.0
161.0
195.7
218.8
 
Typical Fuel Consumption
Power Rating % 1500 rev/min 1800 rev/min
litres/hr UK gal/hr litres/hr UK gal/hr
110 35.3 7.8 38.99 8.6
100 31.5 6.9 36.08 7.9
75 24.1 5.3 27.79 6.1
50 16.6 3.6 19.49 4.3
Note: All engine rating data based on operation under BS551d:1996, ISO 3046/1: l995 and DIN 6271 conditions
 
Test Conditions
Air temperature 25° C (80.6°F), barometric pressure 100 kPa (29.5 in Hg), relative humidity 30%, maximum exhaust back pressure 5 kPa, maximum inlet restriction l kPa.

For operation outside of these conditions please consult your Perkins contact.

Performance tolerance quoted by Perkins is ± 5%

Electrical ratings assume a power factor of 0.8 and a generator efficiency of 90%
 
Rating Definitions
Prime power: Power available at variable load in lieu of main power network. Overload of 10% is permitted for one hour in every 12 hours of operation

Standby (maximum): Power available at variable load in the event of a main power network failure. No overload is permitted