PRODUCTS
|
Engine
speed
rev/min |
Type
of Operation |
Typical
Generator Output |
Nett Engine
Power |
| kVA |
kWe |
kWm |
bhp |
| 1500 |
Prime
Power
Standby Power |
145.9
160.4 |
116.7
128.3 |
125.5
138.0 |
168.2
184.9 |
| 1800 |
Prime
Power
Standby Power |
169.8
187.1 |
135.8
149.7 |
146.0
161.0 |
195.7
218.8 |
|
|
| Typical Fuel Consumption |
| Power
Rating % |
1500
rev/min |
1800 rev/min |
| litres/hr |
UK gal/hr |
litres/hr |
UK gal/hr |
| 110 |
35.3 |
7.8 |
38.99 |
8.6 |
| 100 |
31.5 |
6.9 |
36.08 |
7.9 |
| 75 |
24.1 |
5.3 |
27.79 |
6.1 |
| 50 |
16.6 |
3.6 |
19.49 |
4.3 |
|
|
| Note: All engine rating
data based on operation under BS551d:1996, ISO 3046/1: l995 and DIN 6271 conditions |
| Test
Conditions |
Air temperature 25°
C (80.6°F), barometric pressure 100 kPa (29.5 in Hg), relative humidity
30%, maximum exhaust back pressure 5 kPa, maximum inlet restriction
l kPa.
For operation outside of these conditions please consult your Perkins
contact.
Performance tolerance quoted by Perkins is ± 5%
Electrical ratings assume a power factor of 0.8 and a generator efficiency
of 90% |
|
|
|
| Rating
Definitions |
Prime power: Power available
at variable load in lieu of main power network. Overload of 10% is
permitted for one hour in every 12 hours of operation
Standby (maximum): Power
available at variable load in the event of a main power network failure.
No overload is permitted |
|
|
|
|